Facility: Los Banos Nursing & Rehabilitation (d.b.a. Los Banos Post Acute)
Address: 931 Idaho Ave, Los Banos, CA

The most recent inspection of this food facility resulted in a rating of
Good (Total Points: 0.00)
0-6  Points: Good
7-13 Points: Satisfactory
14+  Points: Unsatisfactory
Rating on date 2-06-2023: Good (Total Points: 0.00)
DateViolationPointsCorrectionInspector CommentsFacility Area
2-06-2023 No violations were noted during this inspection. 0.00 This food facility currently meets California Retail Food Code requirements, and is authorized by the Merced County Division of Environmental Health to be open for business. The permit is issued to the current business owner of record and is non-transferable. no violations observed 0104 LICENSED HEALTH CARE FAC. (16-99 BEDS)


Rating on date 10-16-2019: Satisfactory (Total Points: 8.00)
DateViolationPointsCorrectionInspector CommentsFacility Area
10-16-2019 Toilet facilities shall be maintained clean, sanitary and in good repair. Toilet rooms shall be separated by a well-fitting self-closing door. Toilet tissue shall be provided in a permanently installed dispenser at each toilet. The number of toilet facilities shall be in accordance with local building and plumbing ordinances. Toilet facilities shall be provided for patrons: in establishments with more than 20,000 sq ft.; establishments offering on-site food consumption. (113953, 113953.1, 113953.2, 114250, 114250.1, 114276) 2.00 Provide clean toilet facilities in good repair. Provide permanently installed toilet tissue dispenser(s) in all toilet facilities. Provide handwashing facilities within or adjacent to all toilet facilities. Soap shall be provided in dispensers at, or adjacent to, handwashing facilities. Single-use sanitary towels in dispensers or hot-air blowers shall be provided at handwashing facilities.

Customer restrooms are required for food facilities of more than 20,000 square feet if they were constructed after July 1 1984, and also applies to facilities of any size that were constructed after January 1, 2004 where there is onsite consumption of food. A "take-out only" food facility, with no seating indoors or outdoors, may not be required to provide customer restrooms. Check with the Division of Environmental Health and with the appropriate Planning Department before removing or restricting access to customer restrooms.
EMPLOYEE RESTROOM NEAR THE ENTRANCE: Install a self-closing device on the door.

3 RESIDENT HALLWAY RESTROOMS: The Director of Nursing has cited "fall risks" associated with self-closing devices on the 3 resident restrooms (near Rooms 1, 6, and 15) in the hallway. She stated many residents use assisted devices such as walkers and wheelchairs and she is concerned about the doors hitting the residents and their devices. Due to this concern and only the residents use those restrooms, the self-closing devices will not be required on those doors at this time. Those doors are to be kept closed at all times.
0104 LICENSED HEALTH CARE FAC. (16-99 BEDS)
10-16-2019 Additional information provided to facility operators 0.00 Excerpts from California Health and Safety Code, Division 104 (Environmental Health), Part 7 (California Retail Food Code), sections 113700 through 114437. 1) FOOD SAFETY MANAGER CERTIFICATE: Employee F.O. recently took the exam on August 30, 2019. When the certificate arrives, keep a copy of the certificate on site for review upon request by the inspector.

2) AIR CONDITIONING UNIT IN THE KITCHEN: There were 3 fans in use in the kitchen due to the air conditioning unit being non-functional. Adequate ventilation is required for a reasonable condition of comfort consistent with the employee's job functions. Employee F.O. stated the unit is scheduled to be replaced soon (prior to the next routine inspection).

3) EXHAUST HOOD ABOVE THE AUTOMATIC DISHWASHER: The square ventilation cover was still missing in the unit. Employee stated the unit is scheduled to be replaced soon (prior to the next routine inspection) which is why the cover was not replaced at this time.
0104 LICENSED HEALTH CARE FAC. (16-99 BEDS)
10-16-2019 The walls / ceilings shall have durable, smooth, nonabsorbent, light-colored, and washable surfaces. All floor surfaces, other than the customer service areas, shall be approved, smooth, durable and made of nonabsorbent material that is easily cleanable. Approved base coving shall be provided in all areas, except customer service areas and where food is stored in original unopened containers. Food facilities shall be fully enclosed. All food facilities shall be kept clean and in good repair. (114065, 114067, 114069, 114175, 114143, 114257, 114259.2, 114266, 114268, 114268.1, 114271, 114272) 4.00 All food facilities shall be kept clean, fully operative, and in good repair. Floor surfaces in all areas in which food is prepared, packaged or stored, where any utensil is washed, where refuse or garbage is stored, where janitorial facilities are located, and in all restrooms and hand washing areas shall be smooth and of durable construction and made from non absorbent material that is easily cleanable.

Each permanent food facility shall be fully enclosed in a building consisting of permanent floors, walls, and an overhead structure that meets minimum standards. Food facilities that are not fully enclosed on all sides and that are in operation on January 1, 1985, shall not be required to meet the requirements of this section until the facility is remodeled or has a significant menu change or a change in its method of operation. Full enclosure is not required for dining areas and certain other areas when approved for outdoor food services.
1) 1ST RESIDENT RESTROOM (NEAR ROOM 1) IN THE HALLWAY: Repeat violation. Cracked/deteriorated coved flooring below the aluminum wall panel. Repair or replace. You may submit samples to our office for review prior to purchasing. If unapproved flooring is installed, we may require it to be removed and replaced with the correct flooring, all at the operator's expense.

2) 3rd RESIDENT RESTROOM (NEAR ROOM 15) IN THE HALLWAY: Repeat violation. Cracked/deteriorated coved flooring below the aluminum wall panel. Repair or replace. You may submit samples to our office for review prior to purchasing. If unapproved flooring is installed, we may require it to be removed and replaced with the correct flooring, all at the operator's expense.
0104 LICENSED HEALTH CARE FAC. (16-99 BEDS)
10-16-2019 Exhaust hoods shall be provided to remove toxic gases, heat, grease, vapors, and smoke and be approved by the local building department. Canopy-type hoods shall extend 6" beyond all cooking equipment. All areas shall have sufficient ventilation to facilitate proper food storage. Toilet rooms shall be vented to the outside air by a screened openable window, an air shaft, or a light-switch activated exhaust fan, consistent with local building codes. (114149, 114149.1) Adequate lighting shall be provided in all areas to facilitate cleaning and inspection. Light fixtures in areas where open food is stored, served, prepared, and where utensils are washed shall be of shatterproof construction or protected with light shields. (114149.2, 114149.3, 114252, 114252.1) 2.00 All areas shall have sufficient ventilation to facilitate proper food storage and to provide a reasonable condition of comfort for each employee, consistent with the job performed by the employee.

Light fixtures in areas where food is prepared, open food is stored, or utensils are cleaned shall be of shatterproof construction or shall be protected with shatterproof shields and shall be readily cleanable. In every room and area in which any food is prepared, manufactured, processed, or prepackaged, or in which equipment or utensils are cleaned, sufficient natural or artificial lighting shall be provided to produce the following light intensity, while the area is in use:
(a) At least 10-foot candles for the following:
(1) At a distance of 30 inches above the floor, in walk-in refrigeration units, and dry food storage areas.
(2) At a working surface on which alcoholic beverages are prepared or where utensils used in the preparation or service of alcoholic beverages are cleaned.
(3) Inside equipment, such as reach-in or under-the-counter refrigerators.
(b) At least 20-foot candles for the following:
(1) At a surface where food is provided for consumer self-service or where fresh produce or prepackaged foods are sold or offered for consumption.
(2) In server stations where food is prepared.
(3) At a distance of 30 inches above the floor in areas used for handwashing, warewashing, and equipment and utensil storage, and in toilet rooms.
(c) Except in server stations where food is prepared, at least 50-foot candles at a surface where a food employee is working with food or working with utensils or equipment such as knives, slicers, grinders, or saws where employee safety is a factor.
1) 1ST RESIDENT RESTROOM (NEAR ROOM 1) IN THE HALLWAY: Repair the non-functional ventilation fan in the ceiling.

2) 2ND RESIDENT RESTROOM (NEAR ROOM 6) IN THE HALLWAY: Repair the non-functional ventilation fan in the ceiling.
0104 LICENSED HEALTH CARE FAC. (16-99 BEDS)